Can I put a low-voltage transformer in the attic?












1














I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.



Can I put such transformer in the attic space above the room?



The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)



I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)



Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.



The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.










share|improve this question







New contributor




user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • Being over 55W, the low voltage exemptions won't fully apply.
    – Harper
    9 hours ago


















1














I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.



Can I put such transformer in the attic space above the room?



The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)



I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)



Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.



The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.










share|improve this question







New contributor




user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • Being over 55W, the low voltage exemptions won't fully apply.
    – Harper
    9 hours ago
















1












1








1







I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.



Can I put such transformer in the attic space above the room?



The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)



I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)



Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.



The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.










share|improve this question







New contributor




user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.



Can I put such transformer in the attic space above the room?



The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)



I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)



Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.



The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.







electrical lighting led low-voltage






share|improve this question







New contributor




user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question







New contributor




user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question






New contributor




user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked 10 hours ago









user2907934

162




162




New contributor




user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






user2907934 is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












  • Being over 55W, the low voltage exemptions won't fully apply.
    – Harper
    9 hours ago




















  • Being over 55W, the low voltage exemptions won't fully apply.
    – Harper
    9 hours ago


















Being over 55W, the low voltage exemptions won't fully apply.
– Harper
9 hours ago






Being over 55W, the low voltage exemptions won't fully apply.
– Harper
9 hours ago












2 Answers
2






active

oldest

votes


















2














Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.






share|improve this answer





























    1














    The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.



    The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.



    Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.






    share|improve this answer





















      Your Answer








      StackExchange.ready(function() {
      var channelOptions = {
      tags: "".split(" "),
      id: "73"
      };
      initTagRenderer("".split(" "), "".split(" "), channelOptions);

      StackExchange.using("externalEditor", function() {
      // Have to fire editor after snippets, if snippets enabled
      if (StackExchange.settings.snippets.snippetsEnabled) {
      StackExchange.using("snippets", function() {
      createEditor();
      });
      }
      else {
      createEditor();
      }
      });

      function createEditor() {
      StackExchange.prepareEditor({
      heartbeatType: 'answer',
      autoActivateHeartbeat: false,
      convertImagesToLinks: false,
      noModals: true,
      showLowRepImageUploadWarning: true,
      reputationToPostImages: null,
      bindNavPrevention: true,
      postfix: "",
      imageUploader: {
      brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
      contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
      allowUrls: true
      },
      noCode: true, onDemand: true,
      discardSelector: ".discard-answer"
      ,immediatelyShowMarkdownHelp:true
      });


      }
      });






      user2907934 is a new contributor. Be nice, and check out our Code of Conduct.










      draft saved

      draft discarded


















      StackExchange.ready(
      function () {
      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153439%2fcan-i-put-a-low-voltage-transformer-in-the-attic%23new-answer', 'question_page');
      }
      );

      Post as a guest















      Required, but never shown

























      2 Answers
      2






      active

      oldest

      votes








      2 Answers
      2






      active

      oldest

      votes









      active

      oldest

      votes






      active

      oldest

      votes









      2














      Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.






      share|improve this answer


























        2














        Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.






        share|improve this answer
























          2












          2








          2






          Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.






          share|improve this answer












          Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered 10 hours ago









          Ed Beal

          30.7k12144




          30.7k12144

























              1














              The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.



              The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.



              Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.






              share|improve this answer


























                1














                The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.



                The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.



                Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.






                share|improve this answer
























                  1












                  1








                  1






                  The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.



                  The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.



                  Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.






                  share|improve this answer












                  The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.



                  The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.



                  Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.







                  share|improve this answer












                  share|improve this answer



                  share|improve this answer










                  answered 10 hours ago









                  batsplatsterson

                  9,13811228




                  9,13811228






















                      user2907934 is a new contributor. Be nice, and check out our Code of Conduct.










                      draft saved

                      draft discarded


















                      user2907934 is a new contributor. Be nice, and check out our Code of Conduct.













                      user2907934 is a new contributor. Be nice, and check out our Code of Conduct.












                      user2907934 is a new contributor. Be nice, and check out our Code of Conduct.
















                      Thanks for contributing an answer to Home Improvement Stack Exchange!


                      • Please be sure to answer the question. Provide details and share your research!

                      But avoid



                      • Asking for help, clarification, or responding to other answers.

                      • Making statements based on opinion; back them up with references or personal experience.


                      To learn more, see our tips on writing great answers.





                      Some of your past answers have not been well-received, and you're in danger of being blocked from answering.


                      Please pay close attention to the following guidance:


                      • Please be sure to answer the question. Provide details and share your research!

                      But avoid



                      • Asking for help, clarification, or responding to other answers.

                      • Making statements based on opinion; back them up with references or personal experience.


                      To learn more, see our tips on writing great answers.




                      draft saved


                      draft discarded














                      StackExchange.ready(
                      function () {
                      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153439%2fcan-i-put-a-low-voltage-transformer-in-the-attic%23new-answer', 'question_page');
                      }
                      );

                      Post as a guest















                      Required, but never shown





















































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown

































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown







                      Popular posts from this blog

                      What visual should I use to simply compare current year value vs last year in Power BI desktop

                      Alexandru Averescu

                      Trompette piccolo