Adding separate wire to convert 6-2 Cable to 6-3 Wiring












1














I have an installed but not hooked up 6/2 cable (black, white and ground, like this) in my garage for potential future use with an EV charger. I am finishing the garage and will be covering up the cable but am worried that I might actually need a 6/3 cable instead to support a 14-50 receptacle. I prefer the 14-50 as they seem to be more versatile and common for EV charging than say a 6-50.



Similar questions have asked whether existing 6/2 cabling can be used to hook up to a 14-50 as is, or how to run a new wire in parallel. In my case I have the following additional questions:




  • Is it safe (I know it is possible) to wire up a 14-50R with a 6/2 cable, leaving the neutral terminal empty?

  • Since I still have the walls open, can I run a separate wire like this through the studs alongside the existing 6/2 cable? I.e. am I missing something by not having that wire be part of the sheathing with the 6/2 cable and not armored (as recommended in the linked question above)?










share|improve this question





























    1














    I have an installed but not hooked up 6/2 cable (black, white and ground, like this) in my garage for potential future use with an EV charger. I am finishing the garage and will be covering up the cable but am worried that I might actually need a 6/3 cable instead to support a 14-50 receptacle. I prefer the 14-50 as they seem to be more versatile and common for EV charging than say a 6-50.



    Similar questions have asked whether existing 6/2 cabling can be used to hook up to a 14-50 as is, or how to run a new wire in parallel. In my case I have the following additional questions:




    • Is it safe (I know it is possible) to wire up a 14-50R with a 6/2 cable, leaving the neutral terminal empty?

    • Since I still have the walls open, can I run a separate wire like this through the studs alongside the existing 6/2 cable? I.e. am I missing something by not having that wire be part of the sheathing with the 6/2 cable and not armored (as recommended in the linked question above)?










    share|improve this question



























      1












      1








      1







      I have an installed but not hooked up 6/2 cable (black, white and ground, like this) in my garage for potential future use with an EV charger. I am finishing the garage and will be covering up the cable but am worried that I might actually need a 6/3 cable instead to support a 14-50 receptacle. I prefer the 14-50 as they seem to be more versatile and common for EV charging than say a 6-50.



      Similar questions have asked whether existing 6/2 cabling can be used to hook up to a 14-50 as is, or how to run a new wire in parallel. In my case I have the following additional questions:




      • Is it safe (I know it is possible) to wire up a 14-50R with a 6/2 cable, leaving the neutral terminal empty?

      • Since I still have the walls open, can I run a separate wire like this through the studs alongside the existing 6/2 cable? I.e. am I missing something by not having that wire be part of the sheathing with the 6/2 cable and not armored (as recommended in the linked question above)?










      share|improve this question















      I have an installed but not hooked up 6/2 cable (black, white and ground, like this) in my garage for potential future use with an EV charger. I am finishing the garage and will be covering up the cable but am worried that I might actually need a 6/3 cable instead to support a 14-50 receptacle. I prefer the 14-50 as they seem to be more versatile and common for EV charging than say a 6-50.



      Similar questions have asked whether existing 6/2 cabling can be used to hook up to a 14-50 as is, or how to run a new wire in parallel. In my case I have the following additional questions:




      • Is it safe (I know it is possible) to wire up a 14-50R with a 6/2 cable, leaving the neutral terminal empty?

      • Since I still have the walls open, can I run a separate wire like this through the studs alongside the existing 6/2 cable? I.e. am I missing something by not having that wire be part of the sheathing with the 6/2 cable and not armored (as recommended in the linked question above)?







      wiring






      share|improve this question















      share|improve this question













      share|improve this question




      share|improve this question








      edited 21 hours ago









      Harper

      64.7k341132




      64.7k341132










      asked 22 hours ago









      nodapic

      1205




      1205






















          4 Answers
          4






          active

          oldest

          votes


















          5














          The Code requirement, for good reason, is all conductors must be in the same cable or conduit. I'm not sure whether conduiting this route and stuffing old cable and new wire in the conduit would suffice, that would be up to the local inspector. The conduit would have to be quite large because it would be a nightmare to pull, and because the flat 6-2 cable gets treated same as a round wire of its largest dimension. With 2 "wires" in the conduit, "wires" can only take up 31% of conduit cross section. One thing conduit would be very good for is allowing easy adds and change-ups, extra helpful if you're mudding up the walls! Metal conduit is allowed to serve as the ground wire.



          However I would re-cable with 6-3 rather than risk having the inspector redflag it and have to bust out drywall to fix it.



          There's no reason to tear the 6-2 out of the wall, unless you have another place to use it (not outdoors, mind). Just bring it into a 120mm (4-11/16") junction box ($2.50 at electrical supply, $5 at big-box) and cap it off at both ends. It can be used later for welders, or EV chargers whose labeling/instructions allow use of a 6-20, 6-30 or 6-50 connection.



          You have this. You needed this. Note how many lattés there are in the price difference. I like to use frappucino's (or pizzas) as units of cost savings in cases like this. This case is a glitch, on my screen it shows a $0.02 difference and I suspect normal pricing would put it at 30%.



          I find inexperience + savings seeking = this kind of error. A lot. Before you seal up the walls (why do that at all?? It's a garage) I suggest searching for where else this might have been done.



          In both the examples you linked, you have lifted out of context.




          • The "retrofitting a wire" case, two things wrong there: first it applies only to ground wires, which are a different case because they are not conductors; grounds only carry current during emergencies. And second it applies to old work that was grandfathered because it was legal at the time it was installed. Some people think grandfathering is amnesty for code violations. It's not.

          • In the neutralless 14-50, that case talked about the plug, not the socket. That makes all the difference in the world. The plug is free to take only the conductors it needs, but the socket must proffer all the conductors that its design implies. A neutralless 14-x socket could actually cause a deadly problem if you plug in an appliance that had formerly been wired for NEMA 10.






          share|improve this answer

















          • 1




            Wow, what an excellent answer. Thank you for putting that level of thought into it. In my case the costs are $37 and $80 for 6-2 and 6-3, respectively, but that would be the cost of doing it right, which I am happy to pay. (Maybe you should purchase a ton and re-sell... :) )
            – nodapic
            13 hours ago



















          3














          Safe to run a cable without neutral? Sure. If you have a device that doesn't use a neutral then that is perfectly fine.



          OK to run a neutral separate from the hots? No. Others can quote the NEC, but the bottom line is that the wires should all be separate wires together in one conduit or use a /3 cable. There are two issues as I understand it:




          • Making sure that anything that actually uses a neutral always uses the correct neutral.

          • The wires together cancel out each other's magnetic fields. When they are run separately (even a few inches apart) that doesn't happen and, over a long run, can cause problems.


          Note that running a neutral separately (bad!) is very different from running a ground separately (good!). There are a number of reasons why retrofit ground is often a good idea (though likely not permitted in this case, for example, because it is a new installation), and since a ground wire does not normally carry any current, the concerns about magnetic fields, heating, etc. are not the same as with a neutral wire. For related reasons, a ground can often be smaller than the associated hot & neutral wires.



          There is another advantage to running the neutral (properly) now. That gives you the option of installing a subpanel. You can then connect your EV charger to the subpanel and also additional receptacles, lighting, etc.






          share|improve this answer





















          • What happens when a device does expect/use the neutral? Foreseeably this plug would be used for EV chargers and/or RVs.
            – nodapic
            22 hours ago










          • That is the point! Add the neutral now - definitely makes sense to do so. But unless Harper or ThreePhaseEeel says you can do it with a separate wire from the cable, you will need to switch /2 for either /3 or conduit+individual wires.
            – manassehkatz
            21 hours ago



















          1














          Since it's hard to predict future requirements, and since you have the walls open anyway, rip out the cable and install conduit (the flex plastic stuff is easy to install in most situations).



          Then pull the individual wires you need. If ever requirements change then new wires can be pulled.



          And if you don't need the wires yet you can just install the conduit now, saving the actual wires for later.



          (In fact, installing a conduit or two like this is not a bad idea even if you have no anticipated use for it just now. If you need it in the future it will be there.)






          share|improve this answer





























            0














            That wire we need to be protected in a conduit. So put all 4 in the conduit and a tie wrap in the panel identifying it as part of the circuit (4- 2 ungrounded (hots), 1 grounded (neutral), 1 grounding conductor (EGC).






            share|improve this answer








            New contributor




            mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
            Check out our Code of Conduct.














            • 2




              Pulling cable through conduit is a pain in the rear end -- if you're going to run a conduit, you might as well simply get 4 THHNs and run those.
              – ThreePhaseEel
              21 hours ago











            Your Answer








            StackExchange.ready(function() {
            var channelOptions = {
            tags: "".split(" "),
            id: "73"
            };
            initTagRenderer("".split(" "), "".split(" "), channelOptions);

            StackExchange.using("externalEditor", function() {
            // Have to fire editor after snippets, if snippets enabled
            if (StackExchange.settings.snippets.snippetsEnabled) {
            StackExchange.using("snippets", function() {
            createEditor();
            });
            }
            else {
            createEditor();
            }
            });

            function createEditor() {
            StackExchange.prepareEditor({
            heartbeatType: 'answer',
            autoActivateHeartbeat: false,
            convertImagesToLinks: false,
            noModals: true,
            showLowRepImageUploadWarning: true,
            reputationToPostImages: null,
            bindNavPrevention: true,
            postfix: "",
            imageUploader: {
            brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
            contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
            allowUrls: true
            },
            noCode: true, onDemand: true,
            discardSelector: ".discard-answer"
            ,immediatelyShowMarkdownHelp:true
            });


            }
            });














            draft saved

            draft discarded


















            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153379%2fadding-separate-wire-to-convert-6-2-cable-to-6-3-wiring%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown

























            4 Answers
            4






            active

            oldest

            votes








            4 Answers
            4






            active

            oldest

            votes









            active

            oldest

            votes






            active

            oldest

            votes









            5














            The Code requirement, for good reason, is all conductors must be in the same cable or conduit. I'm not sure whether conduiting this route and stuffing old cable and new wire in the conduit would suffice, that would be up to the local inspector. The conduit would have to be quite large because it would be a nightmare to pull, and because the flat 6-2 cable gets treated same as a round wire of its largest dimension. With 2 "wires" in the conduit, "wires" can only take up 31% of conduit cross section. One thing conduit would be very good for is allowing easy adds and change-ups, extra helpful if you're mudding up the walls! Metal conduit is allowed to serve as the ground wire.



            However I would re-cable with 6-3 rather than risk having the inspector redflag it and have to bust out drywall to fix it.



            There's no reason to tear the 6-2 out of the wall, unless you have another place to use it (not outdoors, mind). Just bring it into a 120mm (4-11/16") junction box ($2.50 at electrical supply, $5 at big-box) and cap it off at both ends. It can be used later for welders, or EV chargers whose labeling/instructions allow use of a 6-20, 6-30 or 6-50 connection.



            You have this. You needed this. Note how many lattés there are in the price difference. I like to use frappucino's (or pizzas) as units of cost savings in cases like this. This case is a glitch, on my screen it shows a $0.02 difference and I suspect normal pricing would put it at 30%.



            I find inexperience + savings seeking = this kind of error. A lot. Before you seal up the walls (why do that at all?? It's a garage) I suggest searching for where else this might have been done.



            In both the examples you linked, you have lifted out of context.




            • The "retrofitting a wire" case, two things wrong there: first it applies only to ground wires, which are a different case because they are not conductors; grounds only carry current during emergencies. And second it applies to old work that was grandfathered because it was legal at the time it was installed. Some people think grandfathering is amnesty for code violations. It's not.

            • In the neutralless 14-50, that case talked about the plug, not the socket. That makes all the difference in the world. The plug is free to take only the conductors it needs, but the socket must proffer all the conductors that its design implies. A neutralless 14-x socket could actually cause a deadly problem if you plug in an appliance that had formerly been wired for NEMA 10.






            share|improve this answer

















            • 1




              Wow, what an excellent answer. Thank you for putting that level of thought into it. In my case the costs are $37 and $80 for 6-2 and 6-3, respectively, but that would be the cost of doing it right, which I am happy to pay. (Maybe you should purchase a ton and re-sell... :) )
              – nodapic
              13 hours ago
















            5














            The Code requirement, for good reason, is all conductors must be in the same cable or conduit. I'm not sure whether conduiting this route and stuffing old cable and new wire in the conduit would suffice, that would be up to the local inspector. The conduit would have to be quite large because it would be a nightmare to pull, and because the flat 6-2 cable gets treated same as a round wire of its largest dimension. With 2 "wires" in the conduit, "wires" can only take up 31% of conduit cross section. One thing conduit would be very good for is allowing easy adds and change-ups, extra helpful if you're mudding up the walls! Metal conduit is allowed to serve as the ground wire.



            However I would re-cable with 6-3 rather than risk having the inspector redflag it and have to bust out drywall to fix it.



            There's no reason to tear the 6-2 out of the wall, unless you have another place to use it (not outdoors, mind). Just bring it into a 120mm (4-11/16") junction box ($2.50 at electrical supply, $5 at big-box) and cap it off at both ends. It can be used later for welders, or EV chargers whose labeling/instructions allow use of a 6-20, 6-30 or 6-50 connection.



            You have this. You needed this. Note how many lattés there are in the price difference. I like to use frappucino's (or pizzas) as units of cost savings in cases like this. This case is a glitch, on my screen it shows a $0.02 difference and I suspect normal pricing would put it at 30%.



            I find inexperience + savings seeking = this kind of error. A lot. Before you seal up the walls (why do that at all?? It's a garage) I suggest searching for where else this might have been done.



            In both the examples you linked, you have lifted out of context.




            • The "retrofitting a wire" case, two things wrong there: first it applies only to ground wires, which are a different case because they are not conductors; grounds only carry current during emergencies. And second it applies to old work that was grandfathered because it was legal at the time it was installed. Some people think grandfathering is amnesty for code violations. It's not.

            • In the neutralless 14-50, that case talked about the plug, not the socket. That makes all the difference in the world. The plug is free to take only the conductors it needs, but the socket must proffer all the conductors that its design implies. A neutralless 14-x socket could actually cause a deadly problem if you plug in an appliance that had formerly been wired for NEMA 10.






            share|improve this answer

















            • 1




              Wow, what an excellent answer. Thank you for putting that level of thought into it. In my case the costs are $37 and $80 for 6-2 and 6-3, respectively, but that would be the cost of doing it right, which I am happy to pay. (Maybe you should purchase a ton and re-sell... :) )
              – nodapic
              13 hours ago














            5












            5








            5






            The Code requirement, for good reason, is all conductors must be in the same cable or conduit. I'm not sure whether conduiting this route and stuffing old cable and new wire in the conduit would suffice, that would be up to the local inspector. The conduit would have to be quite large because it would be a nightmare to pull, and because the flat 6-2 cable gets treated same as a round wire of its largest dimension. With 2 "wires" in the conduit, "wires" can only take up 31% of conduit cross section. One thing conduit would be very good for is allowing easy adds and change-ups, extra helpful if you're mudding up the walls! Metal conduit is allowed to serve as the ground wire.



            However I would re-cable with 6-3 rather than risk having the inspector redflag it and have to bust out drywall to fix it.



            There's no reason to tear the 6-2 out of the wall, unless you have another place to use it (not outdoors, mind). Just bring it into a 120mm (4-11/16") junction box ($2.50 at electrical supply, $5 at big-box) and cap it off at both ends. It can be used later for welders, or EV chargers whose labeling/instructions allow use of a 6-20, 6-30 or 6-50 connection.



            You have this. You needed this. Note how many lattés there are in the price difference. I like to use frappucino's (or pizzas) as units of cost savings in cases like this. This case is a glitch, on my screen it shows a $0.02 difference and I suspect normal pricing would put it at 30%.



            I find inexperience + savings seeking = this kind of error. A lot. Before you seal up the walls (why do that at all?? It's a garage) I suggest searching for where else this might have been done.



            In both the examples you linked, you have lifted out of context.




            • The "retrofitting a wire" case, two things wrong there: first it applies only to ground wires, which are a different case because they are not conductors; grounds only carry current during emergencies. And second it applies to old work that was grandfathered because it was legal at the time it was installed. Some people think grandfathering is amnesty for code violations. It's not.

            • In the neutralless 14-50, that case talked about the plug, not the socket. That makes all the difference in the world. The plug is free to take only the conductors it needs, but the socket must proffer all the conductors that its design implies. A neutralless 14-x socket could actually cause a deadly problem if you plug in an appliance that had formerly been wired for NEMA 10.






            share|improve this answer












            The Code requirement, for good reason, is all conductors must be in the same cable or conduit. I'm not sure whether conduiting this route and stuffing old cable and new wire in the conduit would suffice, that would be up to the local inspector. The conduit would have to be quite large because it would be a nightmare to pull, and because the flat 6-2 cable gets treated same as a round wire of its largest dimension. With 2 "wires" in the conduit, "wires" can only take up 31% of conduit cross section. One thing conduit would be very good for is allowing easy adds and change-ups, extra helpful if you're mudding up the walls! Metal conduit is allowed to serve as the ground wire.



            However I would re-cable with 6-3 rather than risk having the inspector redflag it and have to bust out drywall to fix it.



            There's no reason to tear the 6-2 out of the wall, unless you have another place to use it (not outdoors, mind). Just bring it into a 120mm (4-11/16") junction box ($2.50 at electrical supply, $5 at big-box) and cap it off at both ends. It can be used later for welders, or EV chargers whose labeling/instructions allow use of a 6-20, 6-30 or 6-50 connection.



            You have this. You needed this. Note how many lattés there are in the price difference. I like to use frappucino's (or pizzas) as units of cost savings in cases like this. This case is a glitch, on my screen it shows a $0.02 difference and I suspect normal pricing would put it at 30%.



            I find inexperience + savings seeking = this kind of error. A lot. Before you seal up the walls (why do that at all?? It's a garage) I suggest searching for where else this might have been done.



            In both the examples you linked, you have lifted out of context.




            • The "retrofitting a wire" case, two things wrong there: first it applies only to ground wires, which are a different case because they are not conductors; grounds only carry current during emergencies. And second it applies to old work that was grandfathered because it was legal at the time it was installed. Some people think grandfathering is amnesty for code violations. It's not.

            • In the neutralless 14-50, that case talked about the plug, not the socket. That makes all the difference in the world. The plug is free to take only the conductors it needs, but the socket must proffer all the conductors that its design implies. A neutralless 14-x socket could actually cause a deadly problem if you plug in an appliance that had formerly been wired for NEMA 10.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered 20 hours ago









            Harper

            64.7k341132




            64.7k341132








            • 1




              Wow, what an excellent answer. Thank you for putting that level of thought into it. In my case the costs are $37 and $80 for 6-2 and 6-3, respectively, but that would be the cost of doing it right, which I am happy to pay. (Maybe you should purchase a ton and re-sell... :) )
              – nodapic
              13 hours ago














            • 1




              Wow, what an excellent answer. Thank you for putting that level of thought into it. In my case the costs are $37 and $80 for 6-2 and 6-3, respectively, but that would be the cost of doing it right, which I am happy to pay. (Maybe you should purchase a ton and re-sell... :) )
              – nodapic
              13 hours ago








            1




            1




            Wow, what an excellent answer. Thank you for putting that level of thought into it. In my case the costs are $37 and $80 for 6-2 and 6-3, respectively, but that would be the cost of doing it right, which I am happy to pay. (Maybe you should purchase a ton and re-sell... :) )
            – nodapic
            13 hours ago




            Wow, what an excellent answer. Thank you for putting that level of thought into it. In my case the costs are $37 and $80 for 6-2 and 6-3, respectively, but that would be the cost of doing it right, which I am happy to pay. (Maybe you should purchase a ton and re-sell... :) )
            – nodapic
            13 hours ago













            3














            Safe to run a cable without neutral? Sure. If you have a device that doesn't use a neutral then that is perfectly fine.



            OK to run a neutral separate from the hots? No. Others can quote the NEC, but the bottom line is that the wires should all be separate wires together in one conduit or use a /3 cable. There are two issues as I understand it:




            • Making sure that anything that actually uses a neutral always uses the correct neutral.

            • The wires together cancel out each other's magnetic fields. When they are run separately (even a few inches apart) that doesn't happen and, over a long run, can cause problems.


            Note that running a neutral separately (bad!) is very different from running a ground separately (good!). There are a number of reasons why retrofit ground is often a good idea (though likely not permitted in this case, for example, because it is a new installation), and since a ground wire does not normally carry any current, the concerns about magnetic fields, heating, etc. are not the same as with a neutral wire. For related reasons, a ground can often be smaller than the associated hot & neutral wires.



            There is another advantage to running the neutral (properly) now. That gives you the option of installing a subpanel. You can then connect your EV charger to the subpanel and also additional receptacles, lighting, etc.






            share|improve this answer





















            • What happens when a device does expect/use the neutral? Foreseeably this plug would be used for EV chargers and/or RVs.
              – nodapic
              22 hours ago










            • That is the point! Add the neutral now - definitely makes sense to do so. But unless Harper or ThreePhaseEeel says you can do it with a separate wire from the cable, you will need to switch /2 for either /3 or conduit+individual wires.
              – manassehkatz
              21 hours ago
















            3














            Safe to run a cable without neutral? Sure. If you have a device that doesn't use a neutral then that is perfectly fine.



            OK to run a neutral separate from the hots? No. Others can quote the NEC, but the bottom line is that the wires should all be separate wires together in one conduit or use a /3 cable. There are two issues as I understand it:




            • Making sure that anything that actually uses a neutral always uses the correct neutral.

            • The wires together cancel out each other's magnetic fields. When they are run separately (even a few inches apart) that doesn't happen and, over a long run, can cause problems.


            Note that running a neutral separately (bad!) is very different from running a ground separately (good!). There are a number of reasons why retrofit ground is often a good idea (though likely not permitted in this case, for example, because it is a new installation), and since a ground wire does not normally carry any current, the concerns about magnetic fields, heating, etc. are not the same as with a neutral wire. For related reasons, a ground can often be smaller than the associated hot & neutral wires.



            There is another advantage to running the neutral (properly) now. That gives you the option of installing a subpanel. You can then connect your EV charger to the subpanel and also additional receptacles, lighting, etc.






            share|improve this answer





















            • What happens when a device does expect/use the neutral? Foreseeably this plug would be used for EV chargers and/or RVs.
              – nodapic
              22 hours ago










            • That is the point! Add the neutral now - definitely makes sense to do so. But unless Harper or ThreePhaseEeel says you can do it with a separate wire from the cable, you will need to switch /2 for either /3 or conduit+individual wires.
              – manassehkatz
              21 hours ago














            3












            3








            3






            Safe to run a cable without neutral? Sure. If you have a device that doesn't use a neutral then that is perfectly fine.



            OK to run a neutral separate from the hots? No. Others can quote the NEC, but the bottom line is that the wires should all be separate wires together in one conduit or use a /3 cable. There are two issues as I understand it:




            • Making sure that anything that actually uses a neutral always uses the correct neutral.

            • The wires together cancel out each other's magnetic fields. When they are run separately (even a few inches apart) that doesn't happen and, over a long run, can cause problems.


            Note that running a neutral separately (bad!) is very different from running a ground separately (good!). There are a number of reasons why retrofit ground is often a good idea (though likely not permitted in this case, for example, because it is a new installation), and since a ground wire does not normally carry any current, the concerns about magnetic fields, heating, etc. are not the same as with a neutral wire. For related reasons, a ground can often be smaller than the associated hot & neutral wires.



            There is another advantage to running the neutral (properly) now. That gives you the option of installing a subpanel. You can then connect your EV charger to the subpanel and also additional receptacles, lighting, etc.






            share|improve this answer












            Safe to run a cable without neutral? Sure. If you have a device that doesn't use a neutral then that is perfectly fine.



            OK to run a neutral separate from the hots? No. Others can quote the NEC, but the bottom line is that the wires should all be separate wires together in one conduit or use a /3 cable. There are two issues as I understand it:




            • Making sure that anything that actually uses a neutral always uses the correct neutral.

            • The wires together cancel out each other's magnetic fields. When they are run separately (even a few inches apart) that doesn't happen and, over a long run, can cause problems.


            Note that running a neutral separately (bad!) is very different from running a ground separately (good!). There are a number of reasons why retrofit ground is often a good idea (though likely not permitted in this case, for example, because it is a new installation), and since a ground wire does not normally carry any current, the concerns about magnetic fields, heating, etc. are not the same as with a neutral wire. For related reasons, a ground can often be smaller than the associated hot & neutral wires.



            There is another advantage to running the neutral (properly) now. That gives you the option of installing a subpanel. You can then connect your EV charger to the subpanel and also additional receptacles, lighting, etc.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered 22 hours ago









            manassehkatz

            6,6081029




            6,6081029












            • What happens when a device does expect/use the neutral? Foreseeably this plug would be used for EV chargers and/or RVs.
              – nodapic
              22 hours ago










            • That is the point! Add the neutral now - definitely makes sense to do so. But unless Harper or ThreePhaseEeel says you can do it with a separate wire from the cable, you will need to switch /2 for either /3 or conduit+individual wires.
              – manassehkatz
              21 hours ago


















            • What happens when a device does expect/use the neutral? Foreseeably this plug would be used for EV chargers and/or RVs.
              – nodapic
              22 hours ago










            • That is the point! Add the neutral now - definitely makes sense to do so. But unless Harper or ThreePhaseEeel says you can do it with a separate wire from the cable, you will need to switch /2 for either /3 or conduit+individual wires.
              – manassehkatz
              21 hours ago
















            What happens when a device does expect/use the neutral? Foreseeably this plug would be used for EV chargers and/or RVs.
            – nodapic
            22 hours ago




            What happens when a device does expect/use the neutral? Foreseeably this plug would be used for EV chargers and/or RVs.
            – nodapic
            22 hours ago












            That is the point! Add the neutral now - definitely makes sense to do so. But unless Harper or ThreePhaseEeel says you can do it with a separate wire from the cable, you will need to switch /2 for either /3 or conduit+individual wires.
            – manassehkatz
            21 hours ago




            That is the point! Add the neutral now - definitely makes sense to do so. But unless Harper or ThreePhaseEeel says you can do it with a separate wire from the cable, you will need to switch /2 for either /3 or conduit+individual wires.
            – manassehkatz
            21 hours ago











            1














            Since it's hard to predict future requirements, and since you have the walls open anyway, rip out the cable and install conduit (the flex plastic stuff is easy to install in most situations).



            Then pull the individual wires you need. If ever requirements change then new wires can be pulled.



            And if you don't need the wires yet you can just install the conduit now, saving the actual wires for later.



            (In fact, installing a conduit or two like this is not a bad idea even if you have no anticipated use for it just now. If you need it in the future it will be there.)






            share|improve this answer


























              1














              Since it's hard to predict future requirements, and since you have the walls open anyway, rip out the cable and install conduit (the flex plastic stuff is easy to install in most situations).



              Then pull the individual wires you need. If ever requirements change then new wires can be pulled.



              And if you don't need the wires yet you can just install the conduit now, saving the actual wires for later.



              (In fact, installing a conduit or two like this is not a bad idea even if you have no anticipated use for it just now. If you need it in the future it will be there.)






              share|improve this answer
























                1












                1








                1






                Since it's hard to predict future requirements, and since you have the walls open anyway, rip out the cable and install conduit (the flex plastic stuff is easy to install in most situations).



                Then pull the individual wires you need. If ever requirements change then new wires can be pulled.



                And if you don't need the wires yet you can just install the conduit now, saving the actual wires for later.



                (In fact, installing a conduit or two like this is not a bad idea even if you have no anticipated use for it just now. If you need it in the future it will be there.)






                share|improve this answer












                Since it's hard to predict future requirements, and since you have the walls open anyway, rip out the cable and install conduit (the flex plastic stuff is easy to install in most situations).



                Then pull the individual wires you need. If ever requirements change then new wires can be pulled.



                And if you don't need the wires yet you can just install the conduit now, saving the actual wires for later.



                (In fact, installing a conduit or two like this is not a bad idea even if you have no anticipated use for it just now. If you need it in the future it will be there.)







                share|improve this answer












                share|improve this answer



                share|improve this answer










                answered 17 hours ago









                Hot Licks

                35228




                35228























                    0














                    That wire we need to be protected in a conduit. So put all 4 in the conduit and a tie wrap in the panel identifying it as part of the circuit (4- 2 ungrounded (hots), 1 grounded (neutral), 1 grounding conductor (EGC).






                    share|improve this answer








                    New contributor




                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.














                    • 2




                      Pulling cable through conduit is a pain in the rear end -- if you're going to run a conduit, you might as well simply get 4 THHNs and run those.
                      – ThreePhaseEel
                      21 hours ago
















                    0














                    That wire we need to be protected in a conduit. So put all 4 in the conduit and a tie wrap in the panel identifying it as part of the circuit (4- 2 ungrounded (hots), 1 grounded (neutral), 1 grounding conductor (EGC).






                    share|improve this answer








                    New contributor




                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.














                    • 2




                      Pulling cable through conduit is a pain in the rear end -- if you're going to run a conduit, you might as well simply get 4 THHNs and run those.
                      – ThreePhaseEel
                      21 hours ago














                    0












                    0








                    0






                    That wire we need to be protected in a conduit. So put all 4 in the conduit and a tie wrap in the panel identifying it as part of the circuit (4- 2 ungrounded (hots), 1 grounded (neutral), 1 grounding conductor (EGC).






                    share|improve this answer








                    New contributor




                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.









                    That wire we need to be protected in a conduit. So put all 4 in the conduit and a tie wrap in the panel identifying it as part of the circuit (4- 2 ungrounded (hots), 1 grounded (neutral), 1 grounding conductor (EGC).







                    share|improve this answer








                    New contributor




                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.









                    share|improve this answer



                    share|improve this answer






                    New contributor




                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.









                    answered 22 hours ago









                    mtripp

                    1




                    1




                    New contributor




                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.





                    New contributor





                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.






                    mtripp is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
                    Check out our Code of Conduct.








                    • 2




                      Pulling cable through conduit is a pain in the rear end -- if you're going to run a conduit, you might as well simply get 4 THHNs and run those.
                      – ThreePhaseEel
                      21 hours ago














                    • 2




                      Pulling cable through conduit is a pain in the rear end -- if you're going to run a conduit, you might as well simply get 4 THHNs and run those.
                      – ThreePhaseEel
                      21 hours ago








                    2




                    2




                    Pulling cable through conduit is a pain in the rear end -- if you're going to run a conduit, you might as well simply get 4 THHNs and run those.
                    – ThreePhaseEel
                    21 hours ago




                    Pulling cable through conduit is a pain in the rear end -- if you're going to run a conduit, you might as well simply get 4 THHNs and run those.
                    – ThreePhaseEel
                    21 hours ago


















                    draft saved

                    draft discarded




















































                    Thanks for contributing an answer to Home Improvement Stack Exchange!


                    • Please be sure to answer the question. Provide details and share your research!

                    But avoid



                    • Asking for help, clarification, or responding to other answers.

                    • Making statements based on opinion; back them up with references or personal experience.


                    To learn more, see our tips on writing great answers.





                    Some of your past answers have not been well-received, and you're in danger of being blocked from answering.


                    Please pay close attention to the following guidance:


                    • Please be sure to answer the question. Provide details and share your research!

                    But avoid



                    • Asking for help, clarification, or responding to other answers.

                    • Making statements based on opinion; back them up with references or personal experience.


                    To learn more, see our tips on writing great answers.




                    draft saved


                    draft discarded














                    StackExchange.ready(
                    function () {
                    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153379%2fadding-separate-wire-to-convert-6-2-cable-to-6-3-wiring%23new-answer', 'question_page');
                    }
                    );

                    Post as a guest















                    Required, but never shown





















































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown

































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown







                    Popular posts from this blog

                    What visual should I use to simply compare current year value vs last year in Power BI desktop

                    Alexandru Averescu

                    Trompette piccolo